The required minimum fire-resistance rating is two hours , making option C correct. Table 601 assigns a two-hour fire-resistance rating to the primary structural frame in Type IV-C construction. The structural connection between members of that rated frame cannot become a premature failure point in the load path.
IBC Section 2304.10.1 specifically addresses structural connections in Types IV-A, IV-B, and IV-C mass timber construction. Connection protection must provide the fire-resistance performance required for the connected building element. This can be accomplished through protected connection configurations, approved fire testing, or engineering analysis satisfying the applicable code criteria.
The connection includes more than the visible steel plate or bolt. Fasteners, connectors, concealed steel, bearing zones, and portions of the timber participating structurally in the connection must collectively maintain the required performance. A one-hour or 1½-hour connection would undermine a structural frame required to remain functional for two hours. Three hours is the primary-frame rating associated with Type IV-A, not the Type IV-C condition specified here.
The inspector should verify protection thickness, wood cover, gypsum layers, hardware embedment, edge conditions, and approved connection geometry before concealment.
References/Topics: 2021 IBC Table 601; Section 2304.10.1; fire-resistant structural connections in Types IV-A, IV-B, and IV-C.
===============